69
3061344_201509
Technical maintenance
and engineering details
Temperature/pressure drop
0°C
16325 Ω
15°C
7857 Ω
30°C
4028 Ω
60°C
1244 Ω
5°C
12697 Ω
20°C
6247 Ω
40°C
2662 Ω
70°C
876 Ω
10°C
9952 Ω
25°C
5000 Ω
50°C
1800 Ω
80°C
628 Ω
Category
Boiler
CGB-11
CGB-(K)-20
CGB-(K)-24
Category
I
2H
II
2H3P
II
2H3P
Types of connection
1)
Marking „x“ indicates that all flue pipe components are surrounded by combustion air.
Boiler
Type
1)
Operating mode
To be connected to..
Open
flue
Balanced
flue
moisture-resistant
chimney
balanced
flue chimney
balanced flue
routing
acc. to Build
Regs cert. LAF
moisture-
resistant flue
CGB-(K) B23, B33, C13x,
C33x, C43x, C53,
C53x, C83x, C93x
X
X
B33, C53, C83x
C43x
C13x
2)
,
C33x, C53x
C63x
B23, C53x,
C83x, C93x
Sensor resistances
Temperature [
°
C]
Resistance [Ohm]