29
3062347_0309
The cylinder hysteresis regulates the start point for cylinder heating. The greater
the hysteresis, the lower the start temperature.
Example: Set cylinder temperature 60 °C
Cylinder hysteresis 5 K
Cylinder heating commences at 55 °C and ends at 60 °C.
Cylinder hysteresis
Parameter HG15
HG15
5
Factory setting: 5 K
Setting range: 1 to 30 K
Cylinder heating commences as soon as the cylinder temperature sensor
demands heat. The heating circuit pump would be constantly switched OFF, if
the boiler was undersized, the cylinder was scaled-up or if DHW was constantly
drawn. The accommodation cools down signifi cantly. One option enables a max.
cylinder heating time to be specifi ed to limit this effect. The control unit reverts
to heating mode, when the set cylinder heating time has expired and cycles in
the selected rhythm between heating and cylinder heating mode, irrespective
of whether the cylinder has reached its set temperature or not.
Set this parameter to 0 in heating systems with a high DHW consumption, e.g.
hotels, sports facilities etc.
Max. cylinder heating time
Parameter HG20
Factory setting: 2 h
Setting range: 0 to 5 h
HG20
2
The control unit is equipped with an electronic boiler thermostat, with an
adjustable minimum switch-ON temperature. The burner is switched ON subject
to the cycle block if this temperature is not achieved when heat is demanded.
The minimum boiler water temperature TK-min. is also not necessarily achieved
when there is no heat demand.
Minimum boiler water temperature
TK-min.
Parameter HG21
HG21
40
Factory setting: 40 °C
Setting range: 20 to 60 °C
Displaying / modifying control parameters
with Wolf control accessories
This temperature can be enabled at 80 °C, if for commercial reasons a higher
DHW temperature is required.
If pasteurisation (BM) has been enabled, the DHW cylinder will be heated to
65 °C during the fi rst cylinder heating of the day, subject to parameter HG23
being set to this temperature or higher.
Take adequate measures to prevent scalding.
Maximum DHW temperature
Parameter HG23
HG23
65
Factory setting: 65 °C
Setting range: 60 to 80 °C
Note
Summary of Contents for CGG-2-18