35
3062347_0309
Control unit settings after
gas type conversion
ON / OFF switch
DHW temperature
selector
Pressure
gauge
Reset
button
Heating water
temperature
selector
Illuminated
signal ring
Thermometer
- At the system ON / OFF switch, switch the boiler first OFF and then ON again. There must not be any fault
present at the boiler.
- Press the reset button
within the following 30 seconds
and hold it down during the next steps.
- On (CGU) after 5 seconds the currently set gas type is displayed at the signal ring,
see table: Setting gas type.
On (CGG) after 5 seconds the currently set pipe length is displayed at the signal ring.
- Turn the
heating water temperature selector
towards the required gas type and check the setting by means of
the colour of the illuminated signal ring (see table adjusting the gas type).
- The adjustment will only be activated when the reset button is released.
- A successful conversion of the gas type is indicated by a triple flashing yellow/red (0.4 s ON / 1.0 s OFF) of the
signal ring.
Table: Adjusting the gas type
2. Adjusting the control unit:
Check the nozzle pressure after converting the gas type, otherwise material losses and
incorrect functions can occur.
Gas type
Natural gas
LPG
Illuminated ring display
quickly flashing yellow
quickly flashing red
Heating water temperature adjustment
l.h. closing
r.h. end stop
Note
: The adjustment of the gas type can also be done with the BM accessory controller
(Contractor parameter HG12, description see chapter
"Displaying / modifying control parameters with Wolf control accessories").