62
3062347_0309
Troubleshooting
Any faults will be displayed as fault code by Wolf controllers with eBUS capability. To these faults, cause and remedy may be
allocated using the following table. This table is designed to allow your local heating contractor to trace the fault more easily.
Fault
code
Fault
Cause
Remedy
1
TBV excess
temperature
The flow temperature has exceeded the limit for
the TBV shutdown temperature.
Heat exchanger severely contaminated.
Check the system pressure. Check the heating
circuit pump. Check the HC pump step switch.
Vent the heating system. Press reset button.
Clean the heat exchanger.
4
No flame established
No flame established during the burner start.
Check the gas supply line and open the gas valve,
if necessary.
Check the ignition electrode and ignition cable.
Press the reset button.
5
Flame failure during
operation
Flame failure during
flame stabilisation or soft start.
Check CO2 Values. Check ionisation electrode and
cable.
6
TW excess temperature The flow/return temperature has exceeded the
limit for the TW shut-down temperature.
Check the system pressure. Vent the system.
Set the pump to stage 2 or 3.
7
TBA excess
temperature
Maximum flue gas temperature exceeded.
Clean burner, check gas pressures
8
Flue gas damper does
not activate
Flue gas damper or its feedback faulty.
Check lead.
Replace flue gas damper.
Check bridges in junction box.
10
Flow sensor 2 faulty
Sensor 2 for the flow temperature or
the lead is faulty.
Check lead.
Check/replace flow temperature 2.
11
Flame pretence
A flame is recognised before the
burner starts.
Check the ionisation.
Press the reset button.
12
Flow sensor 1 faulty
Sensor 1 for the flow temperature or
the lead is faulty.
Check lead.
Check/replace flow temperature 1.
14
Cylinder sensor faulty
DHW temperature sensor or lead faulty.
Check lead.
Check/replace cylinder sensor.
15
Outside temperature
sensor faulty
The sensor for the outside temperature or
the lead is faulty.
Check lead.
Check/replace outside temperature sensor
22
Lack of air
Differential pressure switch will not switch ON.
Press the reset button; check the silicone hoses
to the differential pressure switch. Check flue gas
system and gas fan.
Check the differential pressure switch.
23
Fault differential
pressure switch
Differential pressure switch does not switch OFF.
Press reset button;
replace the differential pressure switch, if required.
25
Gas fan fault
The gas fan does not reach the set speed.
Press the reset button, check the gas fan lead
cable, check the flue gas fan and replace the gas
fan.
26
Gas fan fault
The gas fan does not stop.
Press the reset button, check the gas fan lead
cable, check the flue gas fan and replace the gas
fan.
40
System pressure switch
fault
The system pressure switch has responded.
Check the system pressure switch.
Check the system pressure.
41
Flow monitoring
Flow temperature 1 > flow temperature 2 + 12 K ,
temperature change too great.
Vent the heating system, check the system
pressure.
Check heating circuit pump.
45
Fault sensor
Flow rate
Lead or sensor faulty or not connected.
Check the lead and replace the sensor, if required.
46
Fault DHW outlet
temperature
Lead or sensor faulty or not connected.
Check the lead and replace the sensor, if required.
52
Max. cylinder heating
time exceeded
The cylinder heating time takes longer than is set.
Check drawing rate, check DHW cylinder.
78
Manifold sensor faulty
The manifold sensor is outside its permitted range. Check manifold sensor, replace.
(The calculation of the set flow temperature
changes according to the flow sensor).
Summary of Contents for CGG-2-18
Page 64: ...64 3062347_0309 Notes ...