14. Balanced flue
With low outside temperatures, the water vapour
contained in the flue gas may condense and freeze
on the flue. Prevent falling ice through on-site meas
-
ures, e.g. the installation of a suitable snow guard.
The flue gas test connectors must remain acces
-
sible for your local flue gas inspector, even after
fitting the ceiling bezels.
Please
note
Fig.: Example: Balanced flue
For concentric balanced flues and standard flues,
use only original Wolf parts.
Prior to installation, read the technical information
regarding the balanced flue.
As regulations in the individual German Federal
States differ, we recommend consulting the rele-
vant authorities and local flue gas inspector prior
to installation.
Please
note
Inspection and testing intervals
The gas condensing boiler is equipped with con-
tinuous self-calibrating control of the combustion
process. Inspection and testing of this gas combus-
tion appliance (flue path) is only required every 3
years [Germany] under the Bundes-KÜO (German
Federal Sweeping and Inspection Act). This must
be done by a flue gas inspector.
Note