38
3064816_201804
21. Heating appliance operating mode/
burner status
Heating appliance operating mode
Display shows
Meaning
Start
Appliance start
Standby
No heating or DHW demand
Combi mode
DHW heating with heat exchanger active, water tap is open
Heating mode
Heating mode, at least one heating circuit demands heat
DHW mode
DHW heating with cylinder, cylinder temperature is below set value
Emissions test
Emissions test mode active, heating appliance running at maximum output
Frost prot htg
Heat generator frost protection function, boiler water temperature below frost
protection limit
Frost prot DHW
Frost protection function of DHW cylinder enabled; cylinder temperature below frost
protection limit
Frost prot.
System frost protection enabled; outside temperature below frost protection limit
Min. combi time
Appliance remains in DHW mode (heat exchanger) for a minimum amount of time
Heating run-on
Heating circuit pump run-on enabled
DHW run-on
Cylinder primary pump run-on enabled
Parallel mode
Heating circuit pump and cylinder primary pump enabled in parallel
Test
Relay test function has been enabled
Cascade
Cascade module in system enabled
BMS
Appliance is controlled by building management system (BMS)
100 % cali
Appliance is calibrating the flue gas system
External disable
External disabling of the heating appliance (input E1 closed; OWHA)
Heating appliance burner status
Display shows
Meaning
OFF
No burner demand
Pre-flush
Fan operation before burner start
Ignition
Gas valves and ignition unit are enabled
Stabilisation
Flame stabilisation after safety time
Soft start
After flame stabilisation in heating mode, the burner runs at low burner power for
the duration of the soft start to prevent cycling
ON
Burner operational
Cycle block
Burner block after a burner cycle for the duration of the cycle block
Bob
Operation without burner, input E1 closed
Fl. gas damper
Awaiting feedback from flue gas damper (input E1)
Spread high
Temperature spread between boiler water temperature sensor and return
temperature sensor too wide
Spread KF
Temperature spread between eHLSC1/eHLSC2 and boiler sensor too wide
Valve test
Gas valve test
Grad. control
Boiler water temperature rising too quickly
Fault
Burner not operational due to a fault
Post-flush
Fan operation after burner shutdown