30
3062547_201802
22 Control - Displaying / modifying
control parameters
The control parameters can only be modified or displayed via Wolf control accessories with eBUS capability. For installation
and procedures, check the operating instructions of the relevant accessories.
Pressing the r.h. rotary selector calls up control level 2, where you can select the menu levels shown in the overview by turning
the rotary selector clockwise.
Pressing the Info key takes you back to the standard display, irrespective of which submenu is currently displayed.
The system also returns to the standard display automatically when no adjustment is made for more than one minute.
All available set and actual temperatures, burner starts and hours run as well as other system values can be displayed. This scan
is identical to that initiated via the Info key.
Parameter overview / settings report
(settings and functions on the following pages)
Parameter
Setting range
Factory setting Individual settings
A09
Frost protection limit
-20 to +10°C
+2°C
A10
DHW parallel mode
0 / 1
0
A14
Maximum DHW temperature
60 to 80 °C
65°C
HG 00
Tube trimming
1 to 5
3
HG01
Burner switching differential
5 to 20K
10K
HG06
Pump operating mode
0 to 3
0
HG07
Boiler circuit pump run-on time
0 to 30min
4 min
HG08
Maximum limit, boiler circuit TV-max
40 to 90°C
75°C
HG09
Burner cycle block
1 to 30 min
10 min
HG13
Programmable input E1
1 to 11
1
HG14
Programmable output A1
0 to 14
0
HG15
Cylinder hysteresis
1 to 30K
5K
HG16
N / A
HG17
N / A
HG19
Run-on time, cylinder charging pump
0 to 10 min
5 min
HG20
Maximum cylinder charging time
0 to 5 h
2 h
HG21
Minimum boiler water temperature T-boiler min.
20 to 90°C
20°C
HG22
Maximum boiler water temperature T-boiler max.
50 to 90°C
80 °C
HG25
Excess boiler water temperature during cylinder
heating
0 to 40K
10K
HG28
Burner operating mode
1 to 5
2
HG 31
Blocking time burner stage 2
0 to 40 min
10 min
A:
- System parameters
HG.: - Boiler parameters
To prevent damage to the heating system, cancel
night setback when outside temperatures fall
below -12 °C. If this requirement is not observed,
ice may form on the flue outlet. Ice parts which
loosen can cause material damage or personal
injury.
Modifications must only be carried out by a
recognised heating contractor or by the Wolf
customer service. Incorrect settings may cause
damage to and system faults at the boiler.
Note
BM programming unit
L.h. rotary selector
Prog. select.
Display
R.h. rotary selector
Temp. selection
Info key
Single cylinder
heating key
Setback key
Heating key