75
3062547_201802
Type
COB-15
COB-15/TS
COB-20
COB-20/TS
COB-29
COB-29/TS
COB-40
Condensing boiler
(Yes/No)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Low temperature boiler (**)
(Yes/No)
No
No
No
No
No
No
No
B11 boiler
(Yes/No)
No
No
No
No
No
No
No
Space heater with CHP
(Yes/No)
No
No
No
No
No
No
No
If yes, with booster heater
(Yes/No)
-
-
-
-
-
-
-
Combi heating appliance
(Yes/No)
No
Yes
No
Yes
No
Yes
No
Information
Symbol
Unit
Rated heating output
P
rated
kW
15
15
20
20
29
29
39
Usable heat at rated heating
output and high temperature
operation (*)
P
4
kW
14.7
14.7
19.6
19.6
29.0
29.0
38,8
Usable heat at 30% of rated
h e a t i n g o u t p u t a n d l o w
temperature operation (**)
P
1
kW
4.4
4.4
5,9
5,9
8.7
8.7
11,6
Auxiliary power consumption at
full load
elmax
kW
0,122
0,122
0,139
0,139
0,174
0,174
0,205
Auxiliary power consumption at
partial load
elmin
kW
0,049
0,049
0,049
0,049
0,062
0,062
0,072
Auxiliary power consumption in
standby
P
SB
kW
0.003
0.003
0.003
0.003
0.003
0.003
0.003
Seasonal central heating
efficiency
n
s
%
91
91
91
91
91
91
92
Efficiency at rated heating output
and high temperature operation (*)
n
4
%
91,2
91,2
91,6
91,6
91,1
91,1
91.9
Efficiency at 30% of rated heating
output and low temperature
operation (**)
n
1
%
97,3
97,3
96,8
96,8
97,1
97,1
97,5
Heat loss on standby
P
stby
kW
0,068
0,068
0,091
0,091
0,099
0,099
0,107
Energy consumption of ignition
flame
P
ing
kW
0.000
0.000
0.000
0.000
0.000
0.000
0.000
Nitrogen oxide emission
NO
x
mg/kWh
74
74
90
90
90
90
84
Specified load profile
(M, L,
XL, XXL)
-
-
XL
-
XL
-
XL
-
Daily power consumption
Qelec
kWh
-
0,393
-
0,369
-
0,341
-
DHW heating energy efficiency
nwh
%
-
83
-
81
-
81
-
Daily fuel consumption
Qfuel
kWh
-
23,020
-
23,832
-
23,775
-
Contact
WOLF GmbH, Industriestrasse 1, 84048 Mainburg, Germany
(*) High temperature operation means a return temperature of 60°C at the boiler inlet and a flow temperature of 80°C at the boiler outlet.
(**) Low temperature operation means a return temperature (at the boiler inlet) of 30°C for condensing boilers, 37°C for low temperature boilers and 50°C for other heating appliances.
41 Technical parameters to EU