Installation information
H
H
If the siphon is provided on site, establish the height of the siphon with reference
to the adjacent diagram.
The effective siphon height H (mm) must be greater than the maximum under-
or overpressure (in Pa) in the air handling unit (1 mmWC = 10 Pa).
The height differential between the unit discharge and the siphon overflow
should also equal H (mm).
Double siphon
(on site)
Ball siphon
h
In order to drain away the condensate reliably, join a ball siphon to the condensate
drain connector onto the drain pan for the cooler/direct evaporator and onto
the KGX/KGXD plate heat exchanger pan.
Please note that a siphon must be fitted to every condensate drain connector.
It is not permissible to join several drains to a common siphon.
The ball siphon is self-filling. A float ball prevents air being drawn in when the
system is dry, so the initial condensate created can fill the siphon. The ball also
acts as a non-return valve and prevents the siphon from being completely drained.
In order to be able to fit the siphon, ensure that the
foundation
is of the correct
height
.
The effective siphon height h (mm) must be greater than the maximum under-
or overpressure at the condensate connector (1 mmWC = 10 Pa).
h = 1.5 x p (mmWC) + 50 mm (min.)
The siphon drain line must not be connected directly to the public sewage
system, but rather must be able to run out freely. Vent longer drain lines to
prevent condensate backing up in the line.
p
Under- or overpressure in mmWC
according to appliance design
50 mm (WC)
Reserve (imprecision in design, evaporation)
1.5
Additional safety factor