39
3062880_0910
1)
Available fan draught:
MGK-130
Q
max
/Q
min
= 200 Pa / 10 Pa
MGK-170, -210, -250, -300
Q
max
/Q
min
= 150 Pa / 10 Pa
2)
Flue DN 160 made from PP with approval number CE 0036CPD9169003
3)
Flue DN 200 made from PP with approval number CE 0036CPD9169003
4)
Use exclusively original Wolf components
Ventilation air / flue gas routing
Implementation versions, condensing boiler
Maximum length
1)
MGK
DN
-130
-170
-210
-250
-300
B23
Flue in a duct and combustion air directly via the boiler
(open flue)
160
2)
50 m
50 m
47 m
35 m
20 m
200
3)
50 m
50 m
50 m
50 m
50 m
B33
Connection to a moisture-resistant chimney with
horizontal connection line
160
2)
Calculation
1)
to EN 13384-1
200
3)
C33
Combustion air supply and flue gas routing via the roof
in a common pressure range
4)
160
2)
Calculation
1)
to EN 13384-1
(See also example C33)
200
3)
C33
Vertical concentric roof outlet through a pitched or flat
roof, vertical concentric balanced flue for installation in a
duct (each balanced flue)
160/
225
15 m
15 m
13 m
8 m
3 m
200/
300
-
-
-
15 m
15 m
C33
Vertical flue for duct installation with horizontal
concentric connection line (length: 2.5 m); balanced flue
160
25 m
16 m
6 m
-
-
200
30 m
32 m
32 m
26 m
32 m
C43
Connection to a moisture-resistant balanced flue
chimney (balanced flue)
160
2)
Calculation
1)
to EN 13384-1
200
3)
C53
Terminals of the ventilation air and flue are in different
pressure ranges (balanced flue)
160
2)
50 m
50 m
47 m
35 m
20 m
200
3)
50 m
50 m
50 m
50 m
50 m
C53
Connection to a flue run on an external wall with a
horizontal concentric connection line (length: 2.5 m);
balanced flue
160/
225
50 m
50 m
35 m
5 m
-
200/
300
-
-
-
50 m
50 m
C63
The flue gas system has not been tested and
certified with the appliance. It must meet the building
requirements of the relevant country.
160
Calculation
1)
to EN 13384-1 (RLU)
200
C83
Connection to a moisture-resistant chimney and
combustion air through an external wall (balanced flue)
160
Calculation
1)
to EN 13384-1
200
Engineering information,
combustion air / flue gas routing