13
3062878_201707
8. BMK standard display
FR
20.03.09
11:02
21.0
11.4 °C
18.5 °C
PRG OPERATING DATA
Esc MENU
ON/OFF
SET VALUE
Here, the current system status is indicated.
AUS
Off via remote control
System shut down via remote control.
All special functions (night ventilation, backup mode
heating / cooling, holiday program, ext. utilisation
time, air quality control, hygrostat function) as well as
all safety functions are active.
Standby
System shut down via enter key on the BMK.
Only safety functions such as frost protection,
weather-compensated heating circuit pump start
and anti-seizing protection are still active.
FR
20.03.09
11:02
21.0
11.4 °C
18.5 °C
PRG OPERATING DATA
Esc MENU
ON/OFF
SET VALUE
Here, the current speed or fan stage is displayed.
Stepped fan runs with stage 2
Variable speed fan
Stepped fan runs with stage 3
Stepped fan runs with stage 1
FR
20.03.09
11:02
21.0
11.4 °C
18.5 °C
PRG OPERATING DATA
Esc MENU
ON/OFF
SET VALUE
BMS mode
The system runs with the set values that are pre-
defined via the BMS. The system is started and shut
down via the BMS.
Here, the current operating mode is indicated.
Manual mode
The system runs with the set values that are pre-
defined via the programming module for manual
mode. In the case of an additional BMS connection,
the set values can be matched via offsets.
7-day program
The system runs with the times and set values that
are pre-defined in the 7-day program. In the case of
an additional BMS connection, the set values can be
matched via offsets.
AUS
Off via external enabling:
System shut down via external enabling.
All special functions are active (night ventilation,
backup mode heating/cooling, ext. utilisation time, air
quality control, hygrostat function) as well as all safety
functions.