16
3062878_201707
9. Operating level 1
9.2 Operating data
Pressing
Prg
leads to the operating data, where pressing
displays the following
set and actual system values in sequence.
Overview:
→ Extract air / set room temperature
→ Set temp. set value transducer
→ Room temperature
→ Extract air temp
→ Set temp, vent. air
→ Vent. air temperature
→ Set value humidity (room / extract air)
→ Set value humidity (ventilation air)
→ Rel. humidity (room)
→ Rel. hum., extract air
→ Rel. hum., vent. air
→ Pressure
→ Flow rate
→ Proportion fresh air
Main menus
Standard settings
Display
Time functions
Contractor
DISPLAY
SELECTION
Esc BACK
9.3 Main menu
By pressing
Esc
Esc
you reach the main menu. There, by pressing
you select from
the menu points displayed in the overview. After selecting the required menu point,
you enter the required sub-menu by pressing . Pressing
Esc
Esc
returns you to the
standard display. If no adjustment is made for more than 2 minutes, the standard
display will return automatically.
Overview:
→
Standard settings
→ Display
→ Time functions
→ Heating contractor
9.3.1 Standard settings
Standard mask
Esc
Main menu
Standard settings
The most fundamental functions of the air handling system, such as 7-day program,
backup mode, night ventilation and natural cooling can be enabled or disabled
here. Furthermore, the set temperature and the fan speed as well as the fresh air
proportion for manual mode are determined in the standard settings.
Pressing
enables you to select the following standard settings in sequence.
GE-01
DISPLAY
SELECTION
Esc BACK
STANDARD SETTING
Set temp value for
manual mode
21.0°C
Set temp value for
manual mode
Pressing highlights the temperature that can then be changed with
in steps
of 0.5 °C. Finally confirm the selected value with .
Please note The selected set temperature only applies in manual mode.
GE-02
DISPLAY
SELECTION
Esc BACK
STANDARD SETTING
< OFF >
Fan, manual mode
Fan stage / fan enable
for manual mode
Pressing changes the fan stage for stepped fans; for variable speed fans the fan
will be enabled or disabled.
Please note The selected value only applies in manual mode.