23
3062878_201707
9. Operating level 1
In all, there are 4 adjustable day programs available (factory setting: T1 = 6 - 18 h /
T2 = 6 - 14 h / T3 = 11 - 14 h and 17 - 22 h / T4 = 0 - 23:59 h). A day program can be
split into a max. of 5 day sections, to each of which a start and end time (resolution
1 min) can be assigned. The 5 day sections can also overlap (see example), i.e. if
one time lies in two or more sections, the set values of the lower section take priority.
4 adjustable values (bars) can each be defined individually as set values, fan stage
or speed, temperature and fresh air rate.
Example:
With this setting, the system will run from 06:00 h until 12:00 h with the settings of
day section 1. From 12:00 h to 12:30 h with the settings of day section 2 and from
12:30 h until 18:00 h with the settings of section 1 again.
Pressing
shows in sequence the 4 day programs. Pressing
highlights the
start time (hours) of the first day section of the selected day program. Pressing
enables you to set the required value. Confirm the selected value with
. At that
time, the cursor jumps to the start time (min), to which you assign the required value
as described above. As a next step, set the end time in the same manner. Once both
times have been defined, the set fan speed, the set temperature and the set fresh
air proportion (if mixer air dampers are installed) should be set using the bars. You
can cancel any time by pressing
Esc
Esc
. In that case, the cursor returns to the home
position where you can either change the day program or exit the day program by
pressing
Esc
Esc
.
Day programs
Day program 1
06:00
18:00
00:00
00:00
00:00
00:00
00:00
00:00
00:00
00:00
Example
Day program 1
06:00
18:00
12:00
12:30
00:00
00:00
00:00
00:00
00:00
00:00
TP-01
TP-01
This is where the set values for temperature, fan speed, pressure, flow rate and fresh
air proportion are assigned to the bars used in the day programs.
Pressing
enables the selection of which control variable should be assigned to
the set value.
Pressing
again shows in sequence the four stages of the control variable. With
, a specific set value can be assigned to the highlighted stages. You can cancel
by pressing
Esc
Esc
. In that case, the cursor returns to the home position (l.h. top corner)
where you can exit the menu by pressing
Esc
Esc
again.
Please note
If a set value transducer is fitted, it will only be active if bars are activated in day
program 4.
Set values
Set values, time program
Temperatures
DISPLAY
SELECTION
Esc BACK
20.0 °C
16.0 °C
21.7 °C
18.5 °C
= Set room transducer
In the holiday program, 5 fixed periods (comprising a date and time) can be defined.
Corresponding set values can be assigned to these periods.
Pressing
enables the selection from the 5 holiday programs. Pressing
highlights the start time for the selected holiday program. First, by pressing
the
date and then the time are set. Confirm the selected day, month, hour and minute
respectively with . Define the end time in the same way.
Finally, the fan speed, temperature and fresh air proportion are assigned to the
selected period, using the set values defined to the bars.
Holiday program
DISPLAY
SELECTION
Esc BACK
Holiday program
UR-01
Holiday time 1
Start:
End:
00:00
00:00
00:00
00:00
Setting the date and time
Pressing several times highlights in sequence the day of the week, the date, the
month, the year, the hour and minutes of the current time. The highlighted value can
be adjusted with
.
Changes from winter to summer time and vice-versa are made automatically.
Date/time
Date/time
dd.mm.yy hh:mm
18 02 09
11 48
Time function
DISPLAY
SELECTION
Esc BACK