26
3062878_201707
10. Operating level 2
wolf-heiztechnik.de
Contractor
Password: 1234
Alarm management
Service
Backup mode
Night ventilation
Limits
Contractor menus
DISPLAY
SELECTION
Esc BACK
10.2 Heating contractor menu
Standard mask
Esc
Main menu
Heating contractor
Setting heating contractor parameters
The Wolf logo will be displayed. Pressing
prompts entry of the heating contractor
password (1234), which can then be changed with
. By confirming with
you
reach the heating contractor menu. There, by pressing
you select from the
menu points displayed. After selecting the required menu point you enter the required
sub-menu by pressing
. Pressing
Esc
Esc
returns you to the standard display. If
no adjustment was made for more than 2 minutes, the standard display will return
automatically.
Overview:
→
Alarm management
→
Service
→
Backup mode
→
Night ventilation
→
Limits
→
Preheat program
→
Pump control
→
Air dampers
→
Cooling
→
Compensation
→
Temperature control
→
Extension time
→
Peak ventilation
→
Air quality
→
Pressure / flow rate ctl
→
Humidity control
→
HR
Ice guard
→
Other…
Filter monitor
Frost protection
Air flow monitoring
Alarm memory
------------------------------
Alarm management menus
DISPLAY
SELECTION
Esc BACK
10.2.1 Alarm management
Standard mask
Esc
Main menu
Heating contractor
Alarm management
Adjusting parameters concerning alarm messages and functions as well as
displaying the alarm history.
Pressing
enables selection between the overview of the illustrated menu points.
After selecting the required parameter you enter the required sub-menu by pressing
.
Overview:
→
Filter monitor
→
Frost protection
→
Air flow monitor
→
Alarm memory