29
3062878_201707
Here, sensor corrections can be carried out.
Sensor adjustment
Sensor adjustment
0.0 K
Room temperature
DISPLAY
SELECTION
Esc BACK
FA-01
Parameter
Setting range
Factory setting
Room temperature
-5 - 5 K
0 K
Vent. air temperature
-5 - 5 K
0 K
Extract air temp
-5 - 5 K
0 K
Outside temperature
-5 - 5 K
0 K
Icing-up temp
-5 - 5 K
0 K
Ventilation air humidity
-20 - 20 % r.h.
0 % r.h.
Rel. humidity (room)
-20 - 20 % r.h.
0 % r.h.
Rel. hum., extract air
-20 - 20 % r.h.
0 % r.h.
Air quality CO
2
-200 - 200 ppm.
0 ppm.
Diff. pressure sensors, supply
air
-100 - 100 Pa
0 Pa
Diff. pressure sensors, extract
air
-100 - 100 Pa
0 Pa
10. Operating level 2
Here, every drive can be activated manually.
Please note As a safety precaution, the parameters for activating the electric
heater bank or the direct evaporator are only shown when the fan
runs (in the case of single stage fans, this must receive a control
signal of at least 2 V).
In the case of flaps that can be either only open or closed, the fan activation
parameters will only be displayed when the flaps are open.
Manual mode
(condition: system switched OFF)
Manual mode
HB-02
Ventilation fan
Stage 1 :
OFF
Stage 2 :
OFF
Stage 3:
OFF
DISPLAY
SELECTION
Esc BACK
Digital inputs
DE-01
Fault, inv. vent. fan
ID15 KLM - M/L
Fault, EC mtr, vent air
ID--
DISPLAY
SELECTION
Esc BACK
Here, all digital inputs (faults, operating messages) are displayed with their current
status (contact closed or contact open).
Digital inputs