30
3062878_201707
10. Operating level 2
Parameter
Setting range
Factory setting
Heating: Enabling
Yes/No
Yes
Heating: Backup temperature
5 - 30
°C
18
°C
Heating: Fan stage
1 - 3
1
Heating: Fan speed
20 - 100 %
50 %
Heating: Pressure
0 - 6000
P
a
250
P
a
Heating: Flow rate
0 - 120,000
m
3
/h
1000
m
3
/h
Cooling: Enabling
Yes/No
Yes
Cooling: Backup temperature
10 - 40 °C
28 °C
Cooling: Fan stage
1 - 3
1
Cooling: Fan speed
20 - 100 %
50 %
Cooling: Pressure
0 - 6000
P
a
250
P
a
Cooling: Flow rate
0 - 120,000
m
3
/h
1000
m
3
/h
10.2.3 Backup mode
(condition: room temperature
sensor present)
Backup mode
Heating
DISPLAY
SELECTION
Esc BACK
Enabling:
Backup temperature
(YES)
18.0 °C
SB-01
Standard mask
Esc
Main menu
Heating contractor
Backup
mode
Backup mode is active if Enabling = YES and the system is in the operating mode
OFF, either via the time program, manual mode or BMS mode.
A room temperature can be entered respectively for "Backup temperature, heating"
and "Backup temperature, cooling". "Backup mode, heating" is activated when the
actual room temperature falls below the value for "Backup temperature, heating".
For this, the fan is switched to a pre-selected stage (in the case of multi-stage fans),
speed (in the case of variable speed fans), pressure (in the case of pressure control)
or flow rate (in the case of flow rate control). The supply air temperature is regulated
to the maximum supply air temperature. "Backup mode, cooling" will be activated if
the actual room temperature exceeds the value for "Backup temperature, cooling".
For this, the fan is switched to a pre-selected stage (in the case of multi-stage fans),
speed (in the case of variable speed fans), pressure (in the case of pressure control)
or flow rate (in the case of flow rate control). The supply air temperature is regulated
to the minimum supply air temperature.