34
3062878_201707
10. Operating level 2
Standard mask
Esc
Main menu
Heating contractor
Pump
control
The heating circuit / cooling circuit pumps can be operated in various modes.
Heating circuit pump:
- Demand-dependent (on where there is heat demand, otherwise off).
- Weather-compensated: where outside temperature < set value, pump on.
- Constant operation: pump always on when the system is operational.
Cooling circuit pump:
- Demand-dependent (on where there is cooling demand, otherwise off).
- Constant operation: pump always on when the system is operational.
You may also set a run-on time for both pumps.
Parameter
Setting range
Factory setting
Pump, DHW, operating mode:
Demand-dependent /
Outside temperature
/ Constant operation
Demand-
dependent
Pump, DHW, limit, outside temperature
-20 - 15 °C
2 °C
Heating valve control with weather-
compensated pump operating mode
0 - 100 %
0 %
Min. heating valve control during
operation
0 - 100 %
0 %
Pump, DHW, run-on time
0 - 60 min
2 min
Pump, cold water, operating mode:
Demand-dependent /
Constant operation
Demand-
dependent
Pump, cold water, run-on time
0 - 60 min
2 min
Pump reheater bank run-on time
0 - 60
min.
2
min.
Cyclical pump start
0:00 - 23:59 h
5:00 h
After hours
2 - 99
h
24
h
After seconds
0 - 99
s
5
s
10.2.7 Pump control
Pump control
DISPLAY
SELECTION
Esc BACK
Pump, DHW
Operating mode:
Demand-dependent
PS-01