38
3062878_201707
Parameter
Setting range
Factory setting
Switching time for chiller demand,
stage 2
2 - 100 %
50 %
Minimum runtime, stage
0 - 20 min
6 min
Times, stages Minimum ON
0 - 999 s
420 s
Minimum OFF
0 - 999 s
420 s
Switch delay stages,
same direct evaporator
0 - 999 s
0 s
Switch delay stages,
different direct evaporator
0 - 999 s
60 s
High pressure control, refrigerant circuit *
-9.9 - 0 bar
-2.0 bar
Low pressure control, refrigerant circuit *
0 - 9.9 bar
2.0 bar
Max. speed for pressure control *
0 - 100 %
100 %
Switching points, direct evaporator ON
stage 1
- 9.9 - 9.9 K
0.5 K
Switching points, direct evaporator OFF
stage 1
- 9.9 - 9.9 K
- 0.5 K
Switching points, direct evaporator ON
stage 2
- 9.9 - 9.9 K
1.5 K
Switching points, direct evaporator OFF
stage 2
- 9.9 - 9.9 K
- 0.5 K
Compressor block via supply air ON
10 - 24 °C
18 °C
Compressor block via supply air OFF
2 - 20 °C
16 °C
Enable compressor block
Yes/No
Yes
Compressor 1 block via outdoor air ON
0 - 30 °C
0 °C
Compressor 1 block via outdoor air OFF
0 - 30 °C
0 °C
Compressor 2 block via outdoor air ON
0 - 30 °C
0 °C
Compressor 2 block via outdoor air OFF
0 - 30 °C
0 °C
Integrated chiller
Yes/No
No
Fan min. stage
1-3
3
Fan min. speed
20 - 100 %
100 %
Chiller max. output
20 - 100 %
100 %
Chiller max. stage
1 - 2 stage
2 stage
Forced control of the fresh air damper 100 %
Yes/No
Yes
Parameter setting list for "Cooling"
10. Operating level 2