46
3062878_201707
10. Operating level 2
Parameter
Setting range
Factory setting
Prop. fresh air for
hygrostat function
0 - 100 %
100 %
Fan stage for
hygrostat function
1 - 3
3
Fan speed for
hygrostat function
0 - 100 %
80 %
Continuous hygrostat function
Start
0 - 100 % r.h.
60 % r.h.
End
0 - 100 % r.h.
80 % r.h.
Continuous hygrostat function
Max. speed
20 - 100 %
100 %
Continuous hygrostat function
Max. stage
Stage 1-3
Stage 3
Continuous hygrostat function
Max. fresh air rate
0 - 100 %
100 %
Automatic start for
hygrostat function
Yes/No
No
Set humidity level (relative)
10 - 95 % r.h.
50 % r.h.
Set humidity level (absolute)
2 - 30 g/kg
8 g/kg
Max. r.h., vent. air
50 - 100 % r.h.
90 % r.h.
Minimum humidifier control
0 - 100 %
35 %
Minimum humidifier runtime
0 - 99 min
0 min.* / 10 min.**
Humidifier run-on time, drying
0 - 99 min
10 min.* / 2 min.**
Enable below outside
temperature
Yes/No
No
Enable below outside
temperature
0 - 40 °C
15 °C
Delay, temperature priority
control
0 - 60 min
5 min.
Humidifier start delay
0 - 99 min
5 min.* / 2 min.**
Reference temp. for set
humidity level
Actual temperature /
set temperature
Actual temperature
* with adiabatic humidifier
** with isothermal humidifier
To determine the absolute humidity, use the h,x diagram.
As an example, the absolute humidity (9.4 g/kg) at a temperature of 24 °C and a
relative humidity of 50 % has been calculated.
Parameter setting list for
"Humidity control"