3200NT Timer
22
Troubleshooting
Communication Error
If a communication error is detected,
cErr
displays. It may take several minutes for all of the units in a system to
display the error message.
— All units
In Service
remain in the
In Service
position.
— All units in standby go to
In Service
.
— Any unit in regeneration when the error occurs completes regeneration and goes to
In Service
.
— No units are allowed to start a regeneration cycle while the error condition exists.
— When the communication problem is corrected and the error no longer displays (it may take several
minutes for all of the units in a system to stop displaying the error message), the system returns to normal
operation.
NOTE:
During the error condition the control continues to monitor the flow meter and update the remaining
volume. Once the error condition is corrected all units return to the operating status they were in prior
to the error and regeneration is queued according to the normal system operation. If reprogramming
the unit in the Master Programming Mode clears the error, the volume remaining may be reset to the
full unit capacity (i.e. as though it were just regenerated).
NOTE:
System 4 units retain their normal display and do not display
cErr
.
Cause
Correction
A. One or more units have a missing or bad
communication cable.
B. One or more units has a communication
cable plugged into the wrong receptacle.
C. One or more units is not powered.
D. One or more of the units programmed as a
stand alone system 4tc, 4FI or 4Fd and one
or more units programmed as a multi-unit
system 5FI, 6FI, 7FI or 9FI.
E. All of the units programmed as LAg. With no
unit programmed as a LEAd (there is no unit
to start the communications).
A. Connecting the communication cables.
B. Connecting the communication cable as
shown on the wiring diagrams.
C. Powering all units.
D. Programming the units for the same system
type in the Master Programming Mode.
E. Programming the units correctly in the Master
Programming Mode.
Summary of Contents for 3200NT