16
L100001
17
10
�
�
�
�
��
67
���
10
�
�
�
�
��
67
���
5.25
�
�
134
���
8
�
�
�
�
�
216
���
Figure 12 - Vent Opening Requirements
Note: Horizontal runs of vent must
be supported every three feet
(914mm). Use wall straps for this
purpose.
Figure 13 - Rigid Vent Pipe Connections
Female Locking Lugs
Male Slots
REAR WALL VENT INSTALLATION
When installed as a rear vent unit this appliance may be vented directly to a termination located on the rear wall behind
the appliance with 1' of vertical rise minimum.
The maximum horizontal distance between the rear of the appliance and the outside of termination is 20" (508 m).
See
Figure 11.
VENTING INSTALLATION
1. Locate and cut the vent opening in the wall. For com-
bustible walls first frame in opening.
See Figure 11.
Combustible Walls:
Cut a
10
1
⁄
2
"H x
10
1
⁄
2
" W
(
267mm x 267mm
) hole through the exterior wall
and frame as shown.
See Figure 12.
Noncombustible Walls:
Hole opening should be
8
1
⁄
2
" (
216
mm) in diameter.
2. Rigid vent pipes and fittings have special twist-lock
connections. Assemble the desired combination of
pipe and elbows to the appliance adaptor with pipe
seams oriented towards the wall or floor.
Twist-lock Procedure:
The female ends of the pipes
and fittings have three locking lugs (indentations).
These lugs will slide straight into matching slots on
the male end of adjacent pipes and fittings. Push
the pipe sections together and twist one section
clockwise approximately one-quarter turn until the
sections are fully locked.
See Figure 13.
Figure 11 - Rear Vent Application,
Maximum Horizontal Distance
6
6
Maximum
20"
3. Attach vent pipe assembly to the fireplace. Set fire-
place in front of its permanent location to insure
minimum clearances. Mark the wall for a
10
1
⁄
2
"H
x
10
1
1
/
2
" [
216
mm] diameter hole is accept-
able).
See Figure 11.
The center of the hole should
line up with the center line of the horizontal rigid
vent pipe end. Be sure to allow for minimum rise. Cut a
10-
1/2"x10-1/2" (267mm X 267mm)
square
hole through combustible
exterior wall (
8
1
/
2
" [
216
mm] diameter hole if noncombustible). Frame as necessary. Allow
⁄
2
"W
(
267mm x 267mm
)
square
hole
(for noncombustible material such as masonry
block or concrete, a
8
/
4"
minimum rise per foot.
See
1
1