715-0025 v 1.04 CCB # 33
5136-DNS-200X DeviceNet Slave Adapter User’s Guide
© 1999-2002 SST, a division of Woodhead Canada Limited
37
Use, duplication or disclosure of this document or any of the information contained herein is subject to the restrictions
established on page ii of this document.
37
•
From load voltage - total ( output modules
on module bus)
To 40 ºC, 10 A max.
To 55 ºC, 8 A max.
•
From load voltage - ET200X-4O only
To 40 ºC, 6 A max.
To 55 ºC, 4 A max.
Electrical Isolation
Insulation test voltage
500 VDC
Between backplane bus and electronic components
No
Between channels and backplane bus
No – inputs
Yes - outputs
Between channels and supply voltage for electronic
components
No – inputs
Yes - outputs
Between channels
No
Between load power supply and all other circuit components
NA - inputs
Yes – outputs
Between DeviceNet™ and all other circuit components
Yes
Permissible Potential Difference
Between different circuits
75 VDC, 60 VAC
Module power dissipation
4 W max.
NOTE
24 VDC power for module power, network interface power, input current and output load current is
provided by user-supplied Class 2 power supplies. The 5136-DNS-200X routes 24 VDC from the
adapter module and load power connections to modules on the module bus. Power for 24 VDC inputs
may be drawn directly from the input connectors. Additional power modules may be added for more
24 VDC output load current if the adapter module load current limit is exceeded.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com