715-0025 v 1.04 CCB # 33
5136-DNS-200X DeviceNet Slave Adapter User’s Guide
© 1999-2002 SST, a division of Woodhead Canada Limited
39
Use, duplication or disclosure of this document or any of the information contained herein is subject to the restrictions
established on page ii of this document.
39
7.1.2 200X-4DO Technical Data
ET200X Outputs
Sensor Selection Data
Number Outputs
4
Output Voltage
With signal "1"
Load voltage -0.8 V min.
Output Current*
To 40 C max. 0.8A
To 55 C max. 0.6A
With signal "1" rated value
Permissible range
2 A
5 mA to 2.4 A
With signal "0" (residual current)
0.5 mA max.
Load Resistance Range
12 Ohms to 4k Ohms
Lamp Load
10 W max.
Parallel connection of 2 outputs
For redundant control of load
Possible (outputs of same basic module
only)
For performance improvement
Not possible
Driving a digital input
Possible
Switching Frequency
Resistive load
100 Hz max.
Inductive load to IEC947-5-1, DC13
0.5 Hz max
Lamp load
1 Hz max.
Limitation (internal) of voltage induced on
circuit interruption
Load voltage - 47 V typ.
Short-circuit protection for output
Yes, electronic
Response threshold
3 A typ.
* Please note total current per 200X Head
Module