background image

LOCATING  THE  STOVE

Page 5

    WoodPRO™

1.  The stove must be placed on solid concrete, solid 

masonry, or when installed on a combustible 

floo

r, 

on an Underwriters Laboratories Listed Type 2 

oor 

protector listed to UL standard UL 1618, such as 
Hy-C or Imperial Model UL4056BK. Floor protector 
must be 1/2

˝

/13mm minimum thickness (R value 

= 1.19, K value = 0.84 see page 23 for calculation 
formulas) non-combustible material or equivalent. 
The 

floor

 protector must extend at least 

18˝/46cm 

beyond the front of the access door, 

8˝/21cm

 to 

the  sides,  8

˝/

21cm  beyond  the  rear  and  must 

extend under and 

2˝/50mm

 beyond either side of 

the stove pipe if it is elbowed towards a wall. (See 

figures

 4 – 6 and consult local building codes and 

fire protection ordinance

s.)

CAUTION:  FIRE  HAZARD.  CARPETING  AND 

OTHER  COMBUSTIBLE  MATERIAL  SHALL 

NOT COVER THE FLOOR PROTECTOR. THESE 

MATERIALS MUST REMAIN OUTSIDE OF COM-

BUSTIBLE CLEARANCES, SEE FIG. 4 – 6

2.  The room in which the stove is installed must have 

a minim

um floor to ceiling height of 7 ft

. (2.13 m).

3.  The  stove  must  have  its  own 

ue.  Do  not  con-

nect  this  unit  to  a  chimney  flue  serving  other  
appliances. 

DO  NOT  CONNECT TO  ANY  AIR 

DISTRIBUTION DUCT OR SYSTEM.

4.  After  observing  the  clearances  to  combus-

tible  materials  (

gures  4  –  6),  locate  your 

oor  

protector  accordingly  (figure  4)  and  careful-
ly  place  the  stove  in  your  selected  location.   
Install  connector  pipe,  elbows,  and  th

  

s

a

 

e

l

b

m

i

required,  utilizing  either  a  recently  cleaned  and 
inspected 

6˝/152mm

 lined masonry chimney or a 

6

˝/

152mm i.d. manufactured chimney system listed 

to UL 103 HT (US)/ULC-S629 (CAN).

5.  Use round 6

˝/

152mm  dia., minimum 24 MSG black 

or 26 MSG blue steel stove pipe to connect the 
stove to the chimney. Do not use galvanized stove 
pipe. 

NOTE: Mobile home installations require 

double-wall  UL  103  HT  high-temp  connector 

pipe. Secure connector pipe to the 

flue

 collar with 

three  (3)  equally  spaced  sheet  metal  screws  to 

rmly  hold  the  pipe  sections  together.  DO 

N

OT 

CONNECT

 THIS STO

VE

 TO 

ANY

 AIR DISTRIBU-

TION OR DUCT SYSTEM.

6.  Recheck  clearances  from  the  stove,  con-

nector  stove  pipe,  and  corner  clearanc-
es  using  the  illustrations  in  figures  4  –  6  and  
your  local  building  codes  or  fire  protection  
ordinances.

NOTE: ANY WALL CONTAINING COMBUSTI

-

BLE MATERIAL SUCH AS WOODEN STUDS OR 

DRYWALL AND FACED WITH BRICK OR STONE 

MUST  BE  CONSIDERED  A  COMBUSTIBLE 

 

SURFACE.

7.

 

NOTICE: for  installation  in a  manufactured/

mobile home (USA only), please see 

specific 

requirements on page 13.

8.  The  clearances  provided  are  minimum   

dimensions set by US standard UL 1482-2011 & 

ULC-S627-00,

 tested and applied by Polytests

Services,  Inc.  the  manufacturer’s  testing

agency. 

 

Clearances listed and shown MUST be adhered to 
for safe operation of this appliance. 

CLEARANCES 

MAY NOT BE REDUCED BY ANY MEANS IN USA 

OR CANADA.

9

.  This  stove  meets  U.S. Test  Standard:  UL  1482-

2011& Canadian Standard:

 ULC-S627-00.

CAUTION:  KEEP  FURNISHINGS  AND  OTHER   

COMBUSTIBLE MATERIALS AWAY FROM THE 

STOVE.

NOTE:  BEFORE  FIRING WOODSTOVE  SLIDE 

FIREBRICKS TOWARDS THE  REAR  SO  NO 

GAPS REMAIN  BETWEEN BRICKS.

Summary of Contents for WS-TS-1500

Page 1: ...www woodprostoves com 1 877 427 3316 WS TS 1500 WS TS 2000 WS TS 2500 www woodprostoves com www woodprostoves com 4085 112 Rev A ...

Page 2: ...ECT A WOOD BURNING STOVE TO AN ALUMINUM TYPE B GAS VENT This is not safe Use code approved masonry chimney with flue liner or a manufactured Underwriters Laboratories Listed UL 103 HT US ULC S629 CAN Residential Type and Building Heating Ap pliance Chimney Use a 6 152mm diameter chim e e S t f a r d d o o g a e v i g o t h g u o n e h g i h s i t a h t y e n specifics in Chimney Connections instruc...

Page 3: ...ing the fire 27 When adding fuel be careful not to smother the fire Do not build fires against glass and do not load fuel to a height or in such a manner that it creates a hazard when opening the door 28 NEVER LEAVE THE STOVE UNATTENDED with door open Always close the door after ignition 29 DO NOT CONNECT TO OR USE IN CONJUNC TIONWITH ANY AIR DISTRIBUTION DUCTWORK UNLESS SPECIFICALLY APPROVED FOR SUC...

Page 4: ... SERVICE HINTS Preventing Creosote Buildup 20 Chimney Draft 20 21 Glass Care Replacement 21 Door Gasket Replacement 22 BLOWER MAINTENANCE WIRING DIAGRAM 31 BAFFLE REMOVAL 23 24 FLOOR PROTECTOR CALCULATIONS 32 CHIMNEY STOVE MAINTENANCE LOG 33 WARRANTY 34 35 CUSTOMER SERVICE INFORMATION 36 MINIMUM CLEARANCES with SINGLE WALLED PIPE MINIMUM CLEARANCES ALCOVE and DOUBLE WALLED PIPE 6 LOCATING THE STOV...

Page 5: ...red utilizing either a recently cleaned and inspected 6 152mm lined masonry chimney or a 6 152mm i d manufactured chimney system listed to UL 103 HT US ULC S629 CAN 5 Use round 6 152mm dia minimum 24 MSG black or 26 MSG blue steel stove pipe to connect the stove to the chimney Do not use galvanized stove pipe NOTE Mobile home installations require double wall UL 103 HT high temp connector pipe Sec...

Page 6: ...6 Minimum Clearances for installation according to UL 1482 US ULC S627 CAN A ...

Page 7: ...7 Top A A Alcove ...

Page 8: ...philips BLOWER ATTACHMENT 8 4 places A GASKET ...

Page 9: ...9 WS TS 2500 23 8 6 ...

Page 10: ...10 6 ...

Page 11: ...any condensation in the flue to run back into the firebox 2 Horizontal pipe runs must slope upwards towards the chimney at least 1 4 6 4mm per foot of horizontal run 3 You must have at least 18 457mm of clearance between any horizontal piping and the ceiling 4 The pipe cannot extend into the chimney flue figure 8 5 Secure all pipe elbow sections with three 3 equally spaced sheet metal screws at each ...

Page 12: ...trict air supply when the appliance is in operation 6 WARNING DO NOT INSTALL IN A SLEEPING ROOM 7 WARNING DO NOT USE SINGLE WALL CON NECTOR PIPE ANYWHERE IN A MOBILE HOME INSTALLATION A listed double wall chimney connector system ceiling thimble roof thimble spark arrestor and roof ƀCUJKPI suitable for use in Mobile Homes must be used All components of the chimney and connector system must be of t...

Page 13: ...ed for proper drafting to prevent back puffing smoke spillage and to maximize performance Gauges to measure draft are readily available at stove stores and are economical to rent or purchase Factors such as wind barometric pressure trees terrain and chimney temperature can have an adverse effect on the draft The manufacturer cannot be held responsible for external factors leading to less than optim...

Page 14: ...VAC supply stores You may wish to view chimney manufactur ers information on line See www duravent com www selkirkinc com or www mtlfab com VENTING TO EXISTING FIREPLACE In some instances people desire to convert an existing fireplace for stove use Usually safe connec tion to an existing masonry chimney requires more work than using a prefabricated chimney The existing fireplace must be closed and s...

Page 15: ...ller 1 An entry hole must be cut through the masonry and tile liner with minimal damage to the liner At least Figure 14 Fireplace Conversion 8 203mm of liner must remain below the entry position When locating the stove and stovepipe all minimum clearances must be observed from com bustible surfaces including mantels combustible trim work ceilings and walls Positioning the center of the stove pipe ...

Page 16: ...be covered and thimble supported with a sheet steel support minimum 24 gauge in thickness D Chimney Section Pass through Solid insulated listed factory built chimney length with an inside diameter 2 51mm larger than the chimney connec tor and having 1 25 4mm or more of insulation serving as a pass through for a single wall sheet steel chimney connector of minimum 24 gauge thickness with a mini mum...

Page 17: ...ency of the stove and reduces chimney emissions Smoke given off by burning fuel consists of very small organic liquid droplets If these droplets condense they form a sticky tar like substance called creosote When operated properly this stove is designed to burn these droplets Burning these droplets releases heat that would otherwise be lost up the chimney as smoke Following the instructions below ...

Page 18: ...TEMP PAINT WHICH REQUIRES A SERIES OF BURNS TO CURE THE PAINT FOR DURABILITY AND A LIFETIME OF SERVICE Proper curing of the high temp paint requires a series of three initial burns The stove should be allowed to cool off between each burn The first two burns should be small fires and low temperatures 250 F 120 C for a duration of 20 minutes each The third fire should be at a medium high temperatur...

Page 19: ...y but should be kept 1 2 25mm 50mm below the secondary air tubes Also position the fuel to leave space so the air from the inlet can work between the pieces of fuel This reduces the time it takes for new fuel to burn properly 1 When refueling increase the center primary air control to the fully open pulled out position When fire brightens slowly and carefully open the door This procedure will preve...

Page 20: ...20 ...

Page 21: ...21 ...

Page 22: ...nd will need to be replaced Inspect glass and door gaskets periodically to ensure proper seal if gaskets become frayed or worn replace immediately DOOR GASKET REPLACEMENT CAUTION DO NOT OPERATE A STOVETHAT IS MISSING DOOR GASKET MATERIAL OVER FIR ING AND UNSAFE OPERATING CONDITIONS MAY RESULT PROCEDURE 1 Ensure appliance is not in operation and is thor oughly cooled 2 Remove old door gasket and cl...

Page 23: ...23 BAFFLE REMOVAL ...

Page 24: ...24 BAFFLE REMOVAL ...

Page 25: ...SERVICE PARTS 25 ...

Page 26: ...SERVICE PARTS 26 ...

Page 27: ...SERVICE PARTS 27 ...

Page 28: ...SERVICE PARTS 28 ...

Page 29: ...SERVICE PARTS 29 ...

Page 30: ...SERVICE PARTS WS TS 2500 30 ...

Page 31: ... free of dust and dirt NOTICE ANY REPLACE MENT WIRING MUST HAVE EQUIVALENT INSULA TION AND TEMPERATURE RATING 105 C CAUTION MOVING PARTS CAN CAUSE INJURY DO NOT OPERATEWITH COVER REMOVED DANGER SHOCKHAZARD DISCONNECT POWERSOURCEBEFOREINSTALLATION AND WHENEVER SERVICING BLOWER ASSEMBLY BLOWER MAINTENANCE WIRING DIAGRAM 31 ...

Page 32: ...roposed material s b For multiple layers add R values of each layer to determine overall R value 3 If the overall R value of the floor protector system is equal to or greater than the floor protector specifications given the alternate is acceptable Definitions Thermal conductance C BTU W hr ft2 F m2 K Thermal conductivity k Btu inch W Btu hr ft2 F m K hr ft F Thermal resistance R ft2 hr F m2 K Btu W E...

Page 33: ...DATE OF SERVICE PERFORMED BY DESCRIPTION CHIMNEY STOVE MAINTENANCE LOG 33 ...

Page 34: ...Warranty WoodPRO Secondary tubes baffle gaskets Wood Firebox flue collar front door ash door 3 34 ...

Page 35: ...Warranty 35 ...

Page 36: ...36 www woodprostoves com 2 ...

Reviews: