49
LOW LUBE OIL PR SD
—Causes shutdown Relay Output #1 to change state
when oil pressure drops below the OIL SD SET POINT for longer than the OIL
PRESS DELAY time. Shutdown is bypassed when speed is below the SD
BYPASS SPEED, and is armed when speed is above the SD BYPASS SPEED
for the SD BYPASS time.
HI FUEL DEMND SD
—Causes shutdown Relay Output #1 to change state when
the fuel demand exceeds the HI FUEL DEMND SETPT for longer than the HI
FUEL DEMND DELAY time. This shutdown is useful for stopping an engine in an
overload condition.
HI SPEED SD
—Causes shutdown Relay Output #1 to change state when the
engine speed exceeds the HI SPEED SET PNT for longer than the HI SPEED
DELAY time.
LOW WATER PR SD
—Causes shutdown Relay Output #1 to change state when
water pressure drops below the WATER SD SETPOINT for longer than the
WATER PRESS DELAY time. Shutdown is bypassed when speed is below the
SD BYPASS SPEED, and is armed when speed is above the SD BYPASS
SPEED for the SD BYPASS TIME.
HIGH TORSION LVL
—Causes shutdown Relay Output #1 to change state when
the torsional level exceeds the TORS LVL SETPT for longer than the HI
TORSION DLY time.
SD BYPASS SPEED
Speed setting where the Shutdown Bypass is removed
after the SD BYPASS TIME expires to arm all active Alarms and Shutdowns.
SD BYPASS TIME
Sets delay time (in seconds) before the Shutdown Bypass
is removed after the SD BYPASS SPEED is reached.
INDICATION SETUP
This menu allows configuring the function of the Status Indication Relay, Output
#2.
ENERGIZE FOR STATUS
Set TRUE to energize Status Indication Relay and
close Output #2 contact on configured status conditions. Set FALSE to de-
energize Status Indication Relay and open Output #2 contact on configured
status conditions. Default is TRUE.
SPD SW PICKUP
Set speed (rpm) at which the SPEED SWITCH picks up on
increasing speed to indicate status. Default setting is 500 rpm. Status Indication
Relay state is determined by the ENERGIZE FOR STATUS setting.
SPD SW DROPOUT
Set speed (rpm) at which the SPEED SWITCH drops out
on decreasing speed to indicate status. Default setting is 400 rpm. Status
Indication Relay state is determined by the ENERGIZE FOR STATUS setting.
LOAD SW PICKUP
Set % fuel demand at which the LOAD SWITCH picks up
on increasing load to indicate status. Default setting is 99.5%. Status Indication
Relay state is determined by the ENERGIZE FOR STATUS setting.
LOAD SW DROPOUT
Set % fuel demand at which the LOAD SWITCH drops
out on decreasing load to indicate status. Default setting is 99.0%. Status
Indication Relay state is determined by the ENERGIZE FOR STATUS setting.
ALARM SETUP
This menu allows configuring the Alarm conditions which affect the Display
Engine Trouble menu and the function of Engine Trouble Relay, Output #3.
OIL PRESS DELAY
Enter the delay time (in seconds) to wait before the OIL
LOW PR ALM is issued after oil pressure falls below the OIL ALM SETPOINT.
HI FUEL DEMND SETPT
Enter the % Fuel Demand fault level required to
trigger the HI FUEL DEMND ALM.
HI FUEL DEMND DELAY
Enter the delay time (in seconds) to wait before the
HI FUEL DEMND ALM is issued after the % Fuel Demand exceeds the HI FUEL
DEMND SETPT.
Summary of Contents for 723PLUS
Page 8: ...723PLUS Single Engine Marine Propulsion Manual 02880 vi Woodward ...
Page 15: ...Manual 02880 723PLUS Single Engine Marine Propulsion Woodward 7 ...
Page 17: ...Manual 02880 723PLUS Single Engine Marine Propulsion Woodward 9 ...
Page 116: ...723PLUS Single Engine Marine Propulsion Manual 02880 108 Woodward ...