Configuration Notes
•
Refer to Figures 5-6 and 5-7 for analog input wiring.
•
All 4–20 mA inputs have an input impedance of 200
Ω
.
•
When a 4–20 mA input is used, a terminal block jumper must be installed,
per Figure 5-6.
•
The application software must be configured for a 4–20 mA type input, or a
0–5 V type input.
•
Loop power is NOT provided by the Atlas control, it must be sourced
externally.
Analog Outputs
The analog outputs are 4–20 mA with a full scale range of 0–24 mA. The
SmartCore board has four analog outputs.
Atlas
41
42
43
+
4-20 mA
+15 Vdc
A
Figure 5-8. Wiring Example–Analog Output Interface to the SmartCore Board
Configuration Notes
•
Refer to Figure 5-8 for analog output wiring.
•
Only 4–20 mA signals are output.
•
See the specifications section for the maximum analog output load.
•
Care should be taken to prevent ground loops and other faults when
interfacing to non-isolated devices.
•
The output does not contain fault detection. If it is necessary to detect
failures, then the device that is driven by the Analog output, for example an
actuator driver, must contain reference failure detection.
•
The analog outputs have a 15 V common mode voltage, with respect to
AtlasPC control common.