3.4.3
MANual START/STOP
Engine control is separated from breaker management. Breaker(s) must be manually
opened/closed (supply should be in normal range).
MANual Start
Press the MAN button
The LED next to the button will illuminate to confirm the operation
Press the START button
to start the genset as described above. I case
of abnormal conditions, such as overheating, low oil pressure, over speed and abnormal
voltage during generator running occur, the controller can protect genset by stopping
quickly.
MANual Stop
Pressing
can stop the running generator as described above.
3.5
Transition Procedures
3.5.1
Disconnect during cranking
There are three conditions under control to abort the starting of the engine:
• speed sensor
• generator frequency
• engine oil pressure
They can be used separately or in combinations.
We recommend selecting all three at the same time: engine oil pressure together with
speed sensor, and generator frequency. This allows for an immediate separation of the
starter motor from the engine. Additionally, crank disconnect can be checked exactly.
When set to speed sensor, ensure that the number of flywheel teeth is the same as
setting.
Sensor not used? Make sure not to select a sensor that is not in use. Otherwise, an
error message might occur.
22
easYgen-1700
37888A
3 Operation
3.5 Transition Procedures