No
Type
Description
6
Ground fault
If earth fault detection is enabled, the controller it will initiate a trip and stop
alarm if it detects that the earth fault current has exceeded the pre-set value
and the action select “Trip and Stop”.
4.1.5
Trip Alarms
On initiation of the trip condition the controller will de-energize the ‘Close Generator’
Output without stop the generator.
No
Type
Description
1
Gen. overcurrent
The controller will initiate a trip alarm if it detects that the genset current has
exceeded the pre-set value and the selected action is “Trip”.
2
Gen. reverse power
If reverse power detection is enabled, the controller will initiate a trip alarm if it
detects that the reverse power value (power is negative) has fallen below the
pre-set value and the selected action is “Trip”.
3
Overload
If over power detection is enabled, the controller will initiate a trip alarm if it
detects that the over power value (power is positive) has exceeded the pre-set
value and the selected action is “Trip”.
4
Discrete Input
When digit input port is set to “Trip” and the alarm is active, it will initiate a trip
alarm.
5
Ground fault
If earth fault detection is enabled, the controller will initiate a trip alarm if it
detects that the earth fault current has exceeded the pre-set value and the
selected action is “Trip”.
30
easYgen-1700
37888A
4 Appendix
4.1 Alarms and Warnings