Acknowledge alarm
The alarm reset is done with additional (2
nd
time) pressing the mute/acknowledge button
(Alarm LED is no longer flashing).
3.3
Operation Modes
General notes
The easYgen offers three operation modes:
• AUTO
• MANUAL (MAN)
• STOP
• ... and an internal (non) operating phase during the start of the device itself
The operation mode can be initiated – provided the current settings allow for this
function:
• directly by pressing the respective button on the front panel
• directly by click on the respective button on the ToolKit-SC remote screen
• via discrete inputs
• via interface
3.3.1
Operation Mode AUTO
General notes
In operation mode AUTO, both genset and breakers are under easYgen control. The start
and stopping of the engine are managed automatically, along with open, close, and
breaker transition.
• supply load by mains
• supply load by generator
• transition load supply from mains to generator or from generator to mains
• start the engine
• stop the engine
Load supply transition from mains to genset
Situation
• Mains becomes abnormal when one or more parameter are outside their working
range and one of the following occurs:
◦ »Overvoltage«
◦ »Undervoltage«
16
easYgen-1700
37888A
3 Operation
3.3 Operation Modes