Device Parameters
Global Protection Parameters of the System
Parameter
Description
Setting range
Default
Menu path
PSet-Switch
Switching Parameter Set
PS1,
PS2,
PS3,
PS4,
PSS via Inp fct,
PSS via Scada
PS1
[Protection Para
/PSet-Switch]
PS1: activated by
This Setting Group will be the active one if: The
Parameter Setting Group Switch is set to "Switch via
Input" and the other three input functions are inactive at
the same time. In case that there is more than one
input function active, no Parameter Setting Group
Switch will be executed. In case all input functions are
inactive, the device will keep working with the Setting
Group that was activated lastly.
Only available if: PSet-Switch = PSS via Inp fct
1..n, PSS
-.-
[Protection Para
/PSet-Switch]
PS2: activated by
This Setting Group will be the active one if: The
Parameter Setting Group Switch is set to "Switch via
Input" and the other three input functions are inactive at
the same time. In case that there is more than one
input function active, no Parameter Setting Group
Switch will be executed. In case all input functions are
inactive, the device will keep working with the Setting
Group that was activated lastly.
Only available if: PSet-Switch = PSS via Inp fct
1..n, PSS
-.-
[Protection Para
/PSet-Switch]
PS3: activated by
This Setting Group will be the active one if: The
Parameter Setting Group Switch is set to "Switch via
Input" and the other three input functions are inactive at
the same time. In case that there is more than one
input function active, no Parameter Setting Group
Switch will be executed. In case all input functions are
inactive, the device will keep working with the Setting
Group that was activated lastly.
Only available if: PSet-Switch = PSS via Inp fct
1..n, PSS
-.-
[Protection Para
/PSet-Switch]
PS4: activated by
This Setting Group will be the active one if: The
Parameter Setting Group Switch is set to "Switch via
Input" and the other three input functions are inactive at
the same time. In case that there is more than one
input function active, no Parameter Setting Group
Switch will be executed. In case all input functions are
inactive, the device will keep working with the Setting
Group that was activated lastly.
Only available if: PSet-Switch = PSS via Inp fct
1..n, PSS
-.-
[Protection Para
/PSet-Switch]
322
MRU4
DOK-HB-MRU4-2E