Field Parameters
Field Parameters
Field Para
Within the field parameters you can set all parameters, that are relevant for the primary side and the mains
operational method like frequency, primary and secondary values...
General Field Parameters
Parameter
Description
Setting range
Default
Menu path
Phase Sequence
Phase Sequence direction
ABC,
ACB
ABC
[Field Para
/General settings]
f
Nominal frequency
50Hz,
60Hz
50Hz
[Field Para
/General settings]
Field Parameters – Voltage Related
Parameter
Description
Setting range
Default
Menu path
VT pri
Nominal voltage of the Voltage Transformers at the
primary side. The phase to phase voltage is to be
entered even if the load is in delta connection.
60 - 500000V
10000V
[Field Para
/VT]
VT sec
Nominal voltage of the Voltage Transformers at the
secondary side. The phase to phase voltage is to be
entered even if the load is in delta connection.
60.00 - 520.00V
100V
[Field Para
/VT]
VT con
This parameter has to be set in order to ensure the
correct assignment of the voltage measurement
channels in the device.
Phase to Phase,
Phase to Ground
Phase to Ground [Field Para
/VT]
EVT pri
Primary nominal voltage of the e-n winding of the
voltage transformers, which is only taken into account
in the direct measurement of the residual voltage (GVT
con=measured/broken delta).
60 - 500000V
10000V
[Field Para
/VT]
EVT sec
Secondary nominal voltage of the e-n winding of the
voltage transformers, which is only taken into account
in the direct measurement of the residual voltage.
35.00 - 520.00V
100V
[Field Para
/VT]
327
MRU4
DOK-HB-MRU4-2E