Protective Elements
Device Planning Parameters of the Reconnection Module
Parameter
Description
Options
Default
Menu path
Mode
Mode
do not use,
use
do not use
[Device planning]
Global Protection Parameters of the Reconnection Module
Parameter
Description
Setting range
Default
Menu path
ExBlo1
External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.-
[Protection Para
/Global Prot Para
/Intercon-Prot
/ReCon
/General settings]
ExBlo2
External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.-
[Protection Para
/Global Prot Para
/Intercon-Prot
/ReCon
/General settings]
V Ext Release PCC Release Signal by the Point of Common Coupling. The
line-to-line voltage is greater than 95% of VN.
1..n, Assignment
List
-.-
[Protection Para
/Global Prot Para
/Intercon-Prot
/ReCon
/General settings]
PCC Fuse Fail VT
Blocking if the fuse of a voltage transformer has tripped
at the PCC.
1..n, Dig Inputs
-.-
[Protection Para
/Global Prot Para
/Intercon-Prot
/ReCon
/General settings]
reconnected
This signal indicates the state "reconnected" (mains
parallel).
1..n, Assignment
List
-.-
[Protection Para
/Global Prot Para
/Intercon-Prot
/ReCon
/General settings]
Decoupling1
Decoupling function, that blocks the reconnection.
Decoupling
Functions
-.-
[Protection Para
/Global Prot Para
/Intercon-Prot
/ReCon
/Decoupling]
460
MRU4
DOK-HB-MRU4-2E