Protective Elements
Device Planning Parameters of the Intertripping Module
Parameter
Description
Options
Default
Menu path
Mode
Mode
do not use,
use
do not use
[Device planning]
Global Protection Parameters of the Intertripping Module
Parameter
Description
Setting range
Default
Menu path
ExBlo1
External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.-
[Protection Para
/Global Prot Para
/Intercon-Prot
/Mains Decouplg
/Intertripping]
ExBlo2
External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.-
[Protection Para
/Global Prot Para
/Intercon-Prot
/Mains Decouplg
/Intertripping]
ExBlo TripCmd
External blocking of the Trip Command of the
module/the stage, if blocking is activated (allowed)
within a parameter set and if the state of the assigned
signal is true.
1..n, Assignment
List
-.-
[Protection Para
/Global Prot Para
/Intercon-Prot
/Mains Decouplg
/Intertripping]
Alarm
Assignment for External Alarm
1..n, Assignment
List
-.-
[Protection Para
/Global Prot Para
/Intercon-Prot
/Mains Decouplg
/Intertripping]
Trip
External trip of the CB if the state of the assigned signal
is true.
1..n, Assignment
List
-.-
[Protection Para
/Global Prot Para
/Intercon-Prot
/Mains Decouplg
/Intertripping]
495
MRU4
DOK-HB-MRU4-2E