Service and Commissioning Support
Parameter
Description
Setting range
Default
Menu path
VX
Voltage Fundamental Magnitude in Fault State: phase
VX
0.00 - 1.50Vn
0.29Vn
[Service
/Test (Prot inhibit)
/Sgen
/Configuration
/FaultSimulation
/VT]
phi VL1
Start Position respectively Start Angle of the Voltage
Phasor during Fault-Phase:phase L1
-360 - 360°
0°
[Service
/Test (Prot inhibit)
/Sgen
/Configuration
/FaultSimulation
/VT]
phi VL2
Start Position respectively Start Angle of the Voltage
Phasor during Fault-Phase:phase L2
-360 - 360°
240°
[Service
/Test (Prot inhibit)
/Sgen
/Configuration
/FaultSimulation
/VT]
phi VL3
Start Position respectively Start Angle of the Voltage
Phasor during Fault-Phase:phase L3
-360 - 360°
120°
[Service
/Test (Prot inhibit)
/Sgen
/Configuration
/FaultSimulation
/VT]
phi VX meas
Start Position respectively Start Angle of the Voltage
Phasor during Fault-Phase: VX
-360 - 360°
0°
[Service
/Test (Prot inhibit)
/Sgen
/Configuration
/FaultSimulation
/VT]
VL1
Voltage Fundamental Magnitude during Post phase:
phase L1
0.00 - 1.50Vn
0.57Vn
[Service
/Test (Prot inhibit)
/Sgen
/Configuration
/PostFault
/VT]
568
MRU4
DOK-HB-MRU4-2E