Protective Elements
S<
Testing the threshold values
Feed 120% of the S< threshold to the measuring inputs of the relay.
Reduce the fed power slowly until the relay picks up. Compare the measured
value at the time of tripping to the parameterized setting.
Testing the tripping delay
Feed 120% of the S< threshold to the measuring inputs of the relay.
Reduce the fed power with an abrupt change to 80% of the
S< threshold. Measure the tripping delay at the output of the relay.
Successful test result
The measured total tripping delays or individual tripping delays, threshold values
and fallback ratios correspond with those values, specified in the adjustment list.
Permissible deviations/tolerances can be found under Technical Data.