Supervision
Loss of Potential - Fuse Failure
VT Supervision via digital inputs (Fuse Failure)
The module
»LOP« is capable of detecting a fuse failure at the secondary side of the VTs as long as the automatic
circuit breakers of the VTs are connected with the device via a digital input and if this input is assigned to the
module
»LOP«.
Setting the Parameters for detecting a fuse failure (FF) of a phase voltage transformer
In order to detect a fuse failure of a phase voltage transformer via digital input, please proceed as follows:
Assign a digital input onto the parameter »
LOP.Ex FF VT« that represents the state of the automatic circuit
breaker of the phase voltage transformer.
Set the parameter »
Measuring Crcuit Supervison=active« within all those protective elements, that should be
blocked by a fuse failure
.
Setting the Parameters for detecting a fuse failure (FF) of a earth phase voltage transformer
In order to detect a fuse failure of a phase voltage transformer via digital input, please proceed as follows:
Assign a digital input onto the parameter »
LOP.Ex FF EVT« that represents the state of the automatic circuit
breaker of the phase voltage transformer.
Set the parameter »
Measuring Crcuit Supervison=active« within all those protective elements, that should be
blocked by a fuse failure
.
1082
MCDLV4
DOK-HB-MCDLV4-2E
Summary of Contents for HighPROtec MCDLV4
Page 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Page 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Page 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Page 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Page 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Page 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Page 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Page 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Page 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...