Service and Commissioning Support
Application Options of the Fault Simulator
Stop Options
Cold Simulation (Option 1)
Hot Simulation (Option 2)
Manual start, no stop
Run complete:
Pre Failure, Failure, Post Failure.
1.
Call up [S
ervice / Test Mode / Sgen /
Process
]
2.
Ex Force Post = no assignment
3.
Press/Call up
Start
Simulation.
Simulation without tripping the
circuit breaker:
The TripCmd of all protection
functions will be blocked. The
protection function will possibly
trip but not generate a TripCmd.
1.
Call up [Service / Test
Mode / Sgen / Process]
2.
TripCmd Mode = No
TripCmd
Simulation is authorized to trip
the breaker:
1.
Call up [Service / Test
Mode / Sgen / Process]
2.
TripCmd Mode = With
TripCmd
Manual start, stop by external signal
Force Post: As soon as this signal
becomes true, the Fault Simulation will be
forced to switch into the Post Failure mode.
1.
Call up [S
ervice / Test Mode / Sgen /
Process
]
2.
Ex Force Post = Assigned Signal
Manual start, manual stop
As soon as this signal becomes true, the
Fault Simulation will be terminated and the
device changes back to normal operation.
1.
Call up [S
ervice / Test Mode / Sgen /
Process
]
2.
Press/Call up
Stop Simulation.
Start by external signal
The start of the Fault Simulator is triggered
by the assigned external signal (unless a
phase current exceeds 0.1 ⋅ In or the Fault
Simulator is blocked, see also description
above).
1.
Call up [S
ervice / Test Mode / Sgen /
Process
]
2.
Ex Start Simulation = Assigned Signal
1121
MCDLV4
DOK-HB-MCDLV4-2E
Summary of Contents for HighPROtec MCDLV4
Page 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Page 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Page 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Page 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Page 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Page 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Page 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Page 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Page 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...