Energy Counter
Energy Counter
PQSCr
Global Parameters of the Energy Counter Module
Parameter
Description
Setting range
Default
Menu path
S, P, Q Cutoff
Level
The Active/Reactive/Apparent Power shown
in the Display or within the PC Software will
be displayed as zero, if the absolute value of
the corresponding Power falls below this
Cutoff Level. This parameter has no impact
on recorders.
0.0 - 0.100Sn
0.005Sn
[Device Para
/Measurem
Display
/Power]
Power Units
Power Units
Power Auto
Scaling,
kW/kVAr/kVA,
MW/MVAr/MVA,
GW/GVAr/GVA
Power Auto
Scaling
[Device Para
/Measurem
Display
/General
Settings]
Energy Units
Energy Units
Energy Auto
Scaling,
kWh/kVArh/kVA
h,
MWh/MVArh/MV
Ah,
GWh/GVArh/GV
Ah
MWh/MVArh/
MVAh
[Device Para
/Measurem
Display
/General
Settings]
Direct Commands of the Energy Counter Module
Parameter
Description
Setting range
Default
Menu path
Res all Energy
Cr
Reset of all Energy Counters
inactive,
active
inactive
[Operation
/Reset]
Signals of the Energy Counter Module (States of the Outputs)
Signal
Description
Cr Oflw Ws Net
Signal: Counter Overflow Ws Net
Cr Oflw Wp Net
Signal: Counter Overflow Wp Net
Cr Oflw Wp+
Signal: Counter Overflow Wp+
217
MCDLV4
DOK-HB-MCDLV4-2E
Summary of Contents for HighPROtec MCDLV4
Page 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Page 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Page 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Page 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Page 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Page 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Page 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Page 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Page 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...