Installation and Connection
Binary Output Relays
The number of the binary output relay contacts is related to the type of the device or type code. The binary output
relays are potential-free change-over contacts. In chapter
[
Assignment/binary outputs] the assignment of the binary
output relays is specified. The changeable signals are listed in the »assignment list«
which can be found in the
appendix.
Ensure the correct tightening torques.
Please duly consider the current carrying capacity of the binary output relays.
Please refer to the Technical Data.
43
MCDLV4
DOK-HB-MCDLV4-2E
0,56 - 0,79 Nm
5-7 lb·in
0,3 Nm
2.65 lb·in