Switchgear/Breaker – Manager
Monitored Circuit Breaker
SG[3]
Direct Commands of a Monitored Circuit Breaker
Parameter
Description
Setting range
Default
Menu path
Manipulate
Position
WARNING! Fake Position - Manual Position
Manipulation
inactive,
Pos OFF,
Pos ON
inactive
[Control
/SG
/SG[3]
/General
Settings]
Res SGwear Sl
SG
Resetting the slow Switchgear Alarm
inactive,
active
inactive
[Operation
/Reset]
Ack TripCmd
Acknowledge Trip Command
inactive,
active
inactive
[Operation
/Acknowledge]
Global Protection Parameters of a Monitored Circuit Breaker
Parameter
Description
Setting range
Default
Menu path
Aux ON
The CB is in ON-position if the state of the
assigned signal is true (52a).
1..n, DI-
LogicList
-.-
[Control
/SG
/SG[3]
/Pos Indicatrs
Wirng]
Aux OFF
The CB is in OFF-position if the state of the
assigned signal is true (52b).
1..n, DI-
LogicList
-.-
[Control
/SG
/SG[3]
/Pos Indicatrs
Wirng]
Ready
Circuit breaker is ready for operation if the
state of the assigned signal is true. This
digital input can be used by some protective
elements (if they are available within the
device) like Auto Reclosure (AR), e.g. as a
trigger signal.
1..n, DI-
LogicList
-.-
[Control
/SG
/SG[3]
/Pos Indicatrs
Wirng]
551
MCDLV4
DOK-HB-MCDLV4-2E
Summary of Contents for HighPROtec MCDLV4
Page 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Page 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Page 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Page 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Page 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Page 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Page 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Page 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Page 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...