Installation and Connection
Voltage Transformers
Check the installation direction of the VTs.
It is imperative that the secondary sides of measuring transformers be
grounded.
For current and voltage sensing function external wired and appropriate current
and voltage transformer shall be used, based on the required input
measurement ratings. Those devices provide the necessary insulation
functionality.
Check of the Voltage Measuring Values
Connect a three-phase measuring voltage equal to the rated voltage to the relay.
Take connection of the measuring transformers (star connection/open delta
connection) duly into account.
Now adjust voltage values in the nominal voltage range with the corresponding nominal frequency which are not
likely to cause overvoltage- or undervoltage trips.
Compare the values shown in the device display with the readings of the measuring instruments. The deviation
must be according to the technical data.
When r.m.s. value measuring instruments are used, higher deviations can arise
if the fed voltage has a very high harmonic content. Since the device is
provided with a filter for the harmonics, only the fundamental oscillation is
evaluated (exception: thermal protection functions). If, however, a r.m.s. value
forming measuring instrument is used, the harmonics are also measured.
60
MCDLV4
DOK-HB-MCDLV4-2E
Summary of Contents for HighPROtec MCDLV4
Page 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Page 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Page 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Page 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Page 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Page 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Page 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Page 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Page 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...