Protective Elements
Parameter
Description
Setting range
Default
Menu path
IGs>
If the pickup value is exceeded, the
module/stage will be started.
0.002 - 2.000In 0.02In
[Protection
Para
/<1..4>
/I-Prot
/IG[1]]
Char
Characteristic
DEFT,
IEC NINV,
IEC VINV,
IEC EINV,
IEC LINV,
RINV,
ANSI MINV,
ANSI VINV,
ANSI EINV,
Therm Flat,
IT,
I2T,
I4T,
RXIDG
DEFT
[Protection
Para
/<1..4>
/I-Prot
/IG[1]]
t
Tripping delay
Only available if: Characteristic = DEFT
0.00 - 300.00s
0.00s
[Protection
Para
/<1..4>
/I-Prot
/IG[1]]
tchar
Time multiplier/tripping characteristic factor.
The setting range depends on the selected
tripping curve.
Only available if: Characteristic = INV Or
Characteristic = Therm Flat Or
Characteristic = IT Or Characteristic = I2T
Or Characteristic = I4TOr Characteristic =
RXIDG
0.02 - 20.00
1
[Protection
Para
/<1..4>
/I-Prot
/IG[1]]
Reset Mode
Reset Mode
Only available if: Characteristic = INV Or
Characteristic = Therm Flat Or
Characteristic = IT Or Characteristic = I2T
Or Characteristic = I4TOr Characteristic =
RXIDG
instantaneous,
delayed,
calculated
instantaneous [Protection
Para
/<1..4>
/I-Prot
/IG[1]]
738
MCDLV4
DOK-HB-MCDLV4-2E
Summary of Contents for HighPROtec MCDLV4
Page 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Page 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Page 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Page 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Page 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Page 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Page 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Page 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Page 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...