Protective Elements
Setting Group Parameters of the Switch Onto Fault Module
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or deactivation of
module/stage.
inactive,
active
inactive
[Protection
Para
/<1..4>
/SOTF]
ExBlo Fc
Activate (allow) or inactivate (disallow)
blocking of the module/stage. This
parameter is only effective if a signal is
assigned to the corresponding global
protection parameter. If the signal becomes
true, those modules/stages are blocked that
are parameterized "ExBlo Fc=active".
inactive,
active
inactive
[Protection
Para
/<1..4>
/SOTF]
Ex rev Interl Fc Activate (allow) or inactivate (disallow)
blocking of the module/stage. This
parameter is only effective if a signal is
assigned to the corresponding global
protection parameter. If the signal becomes
true, those modules/stages are blocked that
are parameterized "Ex rev Interl Fc =
active".
inactive,
active
inactive
[Protection
Para
/<1..4>
/SOTF]
I<
The CB is in the OFF Position, if the
measured current is less than this
parameter.
0.01 - 1.00In
0.01In
[Protection
Para
/<1..4>
/SOTF]
t-enable
While this timer is running, and while the
module is not blocked, the Switch Onto Fault
Module is effective (SOTF is armed).
0.10 - 10.00s
2s
[Protection
Para
/<1..4>
/SOTF]
771
MCDLV4
DOK-HB-MCDLV4-2E
Summary of Contents for HighPROtec MCDLV4
Page 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Page 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Page 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Page 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Page 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Page 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Page 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Page 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Page 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...