Protective Elements
Parameter
Description
Setting range
Default
Menu path
Alarm Mode
Alarm criterion for the voltage protection
stage.
any one,
any two,
all
any one
[Protection
Para
/<1..4>
/V-Prot
/V[1]]
V>
If the pickup value is exceeded, the
module/element will be started. The
definition of Vn is dependent on both the
Field Parameter »VT con« and the Setting
Group Parameter »Measuring Mode«: If the
measuring inputs of the voltage measuring
card are fed with phase-to-ground voltages
(»VT con« = "Phase-to-Ground") then the
setting »Measuring Mode« = "Phase-to-
Ground" means that Vn=VTsec/SQRT(3),
and »Measuring Mode« = "Phase-to-Phase"
means that Vn=VTsec. However, if the
measuring inputs of the voltage measuring
card are fed with phase-to-phase voltages
(»VT con« = "Phase-to-Phase") then the
setting of "Measuring Mode" is ignored and
internally set to "Phase-to-Phase" instead,
so that Vn=VTsec.
0.01 - 2.000Vn V[1]: 1.1Vn
V[2]: 1.20Vn
V[3]: 1.20Vn
V[4]: 1.20Vn
V[5]: 1.20Vn
V[6]: 1.20Vn
[Protection
Para
/<1..4>
/V-Prot
/V[1]]
V> Reset%
Drop Out (is in percent of setting)
80 - 99%
97%
[Protection
Para
/<1..4>
/V-Prot
/V[1]]
V<
If the pickup value is exceeded, the
module/element will be started. The
definition of Vn is dependent on both the
Field Parameter »VT con« and the Setting
Group Parameter »Measuring Mode«: If the
measuring inputs of the voltage measuring
card are fed with phase-to-ground voltages
(»VT con« = "Phase-to-Ground") then the
setting »Measuring Mode« = "Phase-to-
Ground" means that Vn=VTsec/SQRT(3),
and »Measuring Mode« = "Phase-to-Phase"
means that Vn=VTsec. However, if the
measuring inputs of the voltage measuring
card are fed with phase-to-phase voltages
(»VT con« = "Phase-to-Phase") then the
setting of "Measuring Mode" is ignored and
internally set to "Phase-to-Phase" instead,
so that Vn=VTsec.
0.01 - 2.000Vn V[1]: 0.80Vn
V[2]: 0.9Vn
V[3]: 0.80Vn
V[4]: 0.80Vn
V[5]: 0.80Vn
V[6]: 0.80Vn
[Protection
Para
/<1..4>
/V-Prot
/V[1]]
831
MCDLV4
DOK-HB-MCDLV4-2E
Summary of Contents for HighPROtec MCDLV4
Page 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Page 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Page 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Page 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Page 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Page 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Page 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Page 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Page 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...