Protective Elements
Parameter
Description
Setting range
Default
Menu path
VLL min
Minimum Voltage
0.50 - 1.00Vn
0.70Vn
[Protection
Para
/<1..4>
/Intercon-Prot
/UFLS
/LoadShedding]
Power Angle
Trigger Phi-Power (Positive Phase Sequence
System)
Only available if: UFLS-Method = Power
Angle Supervision
0 - 10°
5°
[Protection
Para
/<1..4>
/Intercon-Prot
/UFLS
/LoadShedding]
P min
Minimum Value (threshold) for the Active
Power
Only available if: UFLS-Method = Pure Active
Power Superv
0.01 - 0.10Sn
0.05Sn
[Protection
Para
/<1..4>
/Intercon-Prot
/UFLS
/LoadShedding]
f<
Underfrequency threshold
45.00 - 65.00Hz 49.00Hz
[Protection
Para
/<1..4>
/Intercon-Prot
/UFLS
/LoadShedding]
t-UFLS
Tripping delay time
0.00 - 300.00s
0.1s
[Protection
Para
/<1..4>
/Intercon-Prot
/UFLS
/LoadShedding]