Binary Output Relays
Parameter
Description
Setting range
Default
Menu path
Inverting 5
Inverting of the state of
the assigned signal.
inactive,
active
inactive
[Device Para
/Binary Outputs
/BO Slot X2
/BO 2]
Assignment 6
Assignment
1..n, Assignment List
-
[Device Para
/Binary Outputs
/BO Slot X2
/BO 2]
Inverting 6
Inverting of the state of
the assigned signal.
inactive,
active
inactive
[Device Para
/Binary Outputs
/BO Slot X2
/BO 2]
Assignment 7
Assignment
1..n, Assignment List
-
[Device Para
/Binary Outputs
/BO Slot X2
/BO 2]
Inverting 7
Inverting of the state of
the assigned signal.
inactive,
active
inactive
[Device Para
/Binary Outputs
/BO Slot X2
/BO 2]
t-hold
To clearly identify the
state transition of a
binary output relay, the
"new state" is being hold,
at least for the duration of
the hold time.
0.00 - 300.00s
0.03s
[Device Para
/Binary Outputs
/BO Slot X2
/BO 3]
Latched
Defines whether the
Binary Output Relay will
be acknowledged
automatically if the event
is gone or whether the
Binary Output Relay is to
be acknowledged by a
signal/manually.
inactive,
active
inactive
[Device Para
/Binary Outputs
/BO Slot X2
/BO 3]
Page 106