Module: Modbus® (Modbus)
Direct Commands of the Modbus
®
Parameter
Description
Setting range
Default
Menu path
Reset Diagn Cr
All Modbus Diagnosis
Counters will be reset.
inactive,
active
inactive
[Operation
/Reset]
Global Protection Parameters of the Modbus
®
Parameter
Description
Setting range
Default
Menu path
Slave ID
Device address (Slave
ID) within the bus
system. Each device
address has to be unique
within a bus system.
Only available if:Device
planning = RTU
1 - 247
1
[Device Para
/Modbus]
Unit ID
The Unit Identifier is used
for routing. This
parameter is to be set, if
a Modbus RTU and a
Modbus TCP network
should be coupled.
Only available if:Device
planning = TCP
1 - 255
255
[Device Para
/Modbus]
TCP Port Config
TCP Port Configuration.
This parameter is to be
set only if the default
Modubs TCP Port should
not be used.
Only available if:Device
planning = TCP
Default,
Private
Default
[Device Para
/Modbus]
Port
Port number
Only available if:Device
planning = TCP And
Only available if: TCP
Port Config = Private
502 - 65535
502
[Device Para
/Modbus]