Parameters
Operational Modes (access authorization)
Operational Mode – »Display Only«
•
The protection is activated.
•
All data, measuring values, records and counters/meters can be viewed.
Operation Mode – »Parameter Setting and Planning«
In this mode you are able to:
•
edit and set parameters.
•
change device planning details and
•
parameterize and reset operational data (event recorder/fault recorder/power meter/switching cycles).
If the device was not active within the parameter setting mode for a longer
time (can be set between 20 – 3600 seconds) it changes automatically into
»Display Only« mode. (Please refer to the appendix
Module Panel
).
As long as you are within the parameter setting mode you cannot
acknowledge.
In order to change into operation mode »Parameter Setting« please proceed as follows:
1. Mark in the device display the parameter you want to change.
2. Press the softkey »Wrench« to change temporarily into the parameter setting mode.
3. Enter the parameter password.
4. Change the parameter.
5. Change perhaps additional parameters.
As long as you are within the parameter setting mode a wrench icon will be
shown in the upper right corner of the display.
6. For saving the altered parameter:
•
press the »OK« key,
•
confirm by pressing the softkey »Yes«.
1. Then the device changes into mode »Display Only«.
Page 200
EN MRU4 10/09