Module: Trip Control (TripControl)
Parameter
Description
Setting range
Default
Menu path
tmax-ON
Within this time the ON
command has to be
carried out by the CB.
Within this time the
position indicators (check
back signals) have to
change from OFF to ON.
0.00 - 10.00s
0.10s
[Protection Para
/Global Prot Para
/CB
/CB Manager]
Aux ON
The CB is in ON-position
if the state of the
assigned signal is true
(52a).
-.-,
DI Slot X1.DI 1,
DI Slot X1.DI 2,
DI Slot X1.DI 3,
DI Slot X1.DI 4,
DI Slot X1.DI 5,
DI Slot X1.DI 6,
DI Slot X1.DI 7,
DI Slot X1.DI 8
-
[Protection Para
/Global Prot Para
/CB
/CB Manager]
Aux OFF
The CB is in OFF-
position if the state of the
assigned signal is true
(52b).
-.-,
DI Slot X1.DI 1,
DI Slot X1.DI 2,
DI Slot X1.DI 3,
DI Slot X1.DI 4,
DI Slot X1.DI 5,
DI Slot X1.DI 6,
DI Slot X1.DI 7,
DI Slot X1.DI 8
-
[Protection Para
/Global Prot Para
/CB
/CB Manager]
Manual ON
The circuit breaker was
switched on manually if
the state of the assigned
signal is true.
-.-,
DI Slot X1.DI 1,
DI Slot X1.DI 2,
DI Slot X1.DI 3,
DI Slot X1.DI 4,
DI Slot X1.DI 5,
DI Slot X1.DI 6,
DI Slot X1.DI 7,
DI Slot X1.DI 8
-
[Protection Para
/Global Prot Para
/CB
/CB Manager]
Page 232
EN MRU4 10/09