VE-Protection Module – Residual Voltage [59N]
Setting Group Parameters of the Residual Voltage Supervision Module.
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or
deactivation of module/stage.
inactive,
active
inactive
[Protection Para
/<n>
/V-Prot
/VE[1]]
ExBlo Fc
Activate (allow) or inactivate
(disallow) blocking of the module/
stage. This parameter is only
effective if a signal is assigned to
the corresponding global
protection parameter. If the signal
becomes true, those
modules/stages are blocked that
are parameterized "ExBlo
Fc=active".
inactive,
active
inactive
[Protection Para
/<n>
/V-Prot
/VE[1]]
Blo TripCmd
Permanent blocking of the Trip
Command of the module/stage.
inactive,
active
inactive
[Protection Para
/<n>
/V-Prot
/VE[1]]
ExBlo TripCmd Fc
Activate (allow) or inactivate
(disallow) blocking of the module/
stage. This parameter is only
effective if a signal is assigned to
the corresponding global
protection parameter. If the signal
becomes true, those
modules/stages are blocked that
are parameterized "ExBlo
TripCmd Fc=active".
inactive,
active
inactive
[Protection Para
/<n>
/V-Prot
/VE[1]]
VE>
If the pick-up value is exceeded,
the module/stage will be started.
0.01 - 2.00Vn
1Vn
[Protection Para
/<n>
/V-Prot
/VE[1]]
t
Tripping delay
0.00 - 300.00s
0.00s
[Protection Para
/<n>
/V-Prot
/VE[1]]
EN MRU4 10/09
Page 249